R22 Replacement Refrigerants in the UAE: R407C vs R417A and When to Switch

Quick answer: The two most common R22 replacement gases in the UAE are R407C and R417A. R407C matches R22’s cooling capacity closely, but it needs a switch from mineral oil to POE oil. R417A usually works with the existing oil, but it gives slightly less capacity. Neither is a true drop-in. Both are blends, so you must charge them as liquid and adjust the system after the change. If the compressor has failed or the unit is very old, replacing the whole system is often the better choice.

At Haste Trading, we supply R22 replacement refrigerants, oils and service parts to technicians and facilities teams across Dubai, Sharjah and Abu Dhabi. This guide compares R407C and R417A, explains how a retrofit works, and helps you decide when to switch.

Why Look for an R22 Replacement?

R22 is still legal to buy and use in the UAE. However, its supply keeps shrinking under the Montreal Protocol phase-down. As a result, prices drift upward and availability becomes less predictable.

For an older system that still runs well, a replacement gas can extend its life. It also removes your dependence on a shrinking R22 supply. For current R22 rates, see our R22 gas price guide.

What Makes a Good R22 Replacement?

A good replacement should come close to R22 in four areas:

  • Cooling capacity, so the room or cold store still reaches temperature
  • Operating pressures, so existing components stay within their limits
  • Oil compatibility, so oil keeps returning to the compressor
  • Safety class, ideally A1 (non-flammable), like R22

No single gas wins on all four. That is why the choice usually comes down to R407C or R417A.

R22 Replacement Refrigerants

R407C vs R417A: Which Is the Better R22 Replacement?

Both are zero-ODP HFC-based blends. Still, they suit different jobs.

PropertyR22R407CR417A
TypeHCFC (single component)HFC blend (R32/R125/R134a)HFC/HC blend (R125/R134a/R600)
Ozone depletion potential0.05500
GWP (100-year, IPCC AR4)~1,810~1,774~2,346
Safety classA1A1A1
Capacity vs R22BaselineClose to R22Slightly lower
OilMineralPOE (oil change needed)Usually existing mineral/AB oil
Temperature glideNoneNoticeableNoticeable
How to chargeVapour or liquidLiquid onlyLiquid only

GWP values follow the IPCC AR4 basis. Figures can differ slightly between reports and regulations.

When Should You Choose R407C?

Choose R407C when capacity matters most. It is the closest match to R22 in air conditioning, so a retrofitted split or packaged unit performs much as it did before.

The trade-off is the oil change. R407C does not mix well with mineral oil, so you need to switch to POE oil. That adds labour, but it gives a cleaner long-term result.

Haste stocks R407C from Honeywell in 11.3 kg cylinders and from SEASON in 650 g to 11.3 kg sizes.

When Should You Choose R417A?

Choose R417A when a quick, low-disruption retrofit matters most. Its small hydrocarbon component helps carry mineral oil back to the compressor. So in many systems, you can keep the existing oil.

The trade-off is capacity. R417A typically delivers slightly less cooling than R22. In a unit that already struggles on a 45 °C UAE afternoon, that loss can matter.

You can find SEASON R417A in 11.3 kg cylinders on our R417A refrigerant page.

How Do You Retrofit an R22 System?

A retrofit is more than swapping one gas for another. Follow the gas manufacturer’s retrofit guide for your exact system. In general, the job looks like this.

Step-by-Step R22 Retrofit Overview

  1. Record a baseline. Note pressures, temperatures and current draw while the unit runs on R22.
  2. Recover all the R22. Use a recovery unit and a proper recovery cylinder. Never vent it.
  3. Change the oil if needed. For R407C, replace mineral oil with POE. Some systems need several flushes to remove enough old oil.
  4. Replace the filter drier. Fit a new drier that suits the new refrigerant and oil.
  5. Evacuate the system. Pull a deep vacuum and confirm it holds.
  6. Charge as liquid. Both R407C and R417A are blends, so liquid charging keeps the mix correct.
  7. Adjust and label. Check super heat and adjust the expansion valve if needed. Then label the unit with the new gas and oil.
Why Liquid Charging Matters

R407C and R417A are zeotropic blends, which means their components boil at different temperatures. If you charge from the vapour side, the lighter components leave the cylinder first. The system then ends up with the wrong mix and poor performance.

Why Temperature Glide Changes Your Readings

Both gases show temperature glide. In other words, they boil across a range of temperatures, not at one point. So read super heat using the dew point and sub-cooling using the bubble point. A gauge with the right refrigerant scale makes this easier. Our manifold gauge set guide explains how to read these values.

What Parts and Tools Will You Need?

When Should You Replace the System Instead?

A retrofit makes sense when the system is mechanically sound. In some cases, however, a new system is the smarter spend. Consider replacing when:

  • the compressor has failed or is close to failure
  • the system has repeated or large leaks
  • the unit is near the end of its working life
  • energy bills are high, and a modern R32 or R410A unit would cut running costs

For a fuller repair-or-replace assessment, see our R22 legality and cylinder guide. If you decide on a new split AC, our R32 refrigerant guide explains the gas most new units use.

Can You Use R410A or R32 to Replace R22?

No. R410A and R32 run at much higher pressures than R22. An R22 system’s compressor, coils and pipework are not designed for those pressures. In addition, R32 is mildly flammable (A2L).

So the only safe route to R410A or R32 is a new system designed for that gas.

What Should You Check Before Retrofitting?

  • Confirm the compressor manufacturer approves the replacement gas and oil.
  • Check the system’s age, leak history and general condition.
  • Make sure you can charge from the liquid phase.
  • Budget for a new filter drier and, for R407C, the oil change.
  • Label the unit clearly after the retrofit, so the next technician knows what is inside.

Frequently Asked Questions

What is the best replacement for R22 in the UAE?
For air conditioning, R407C is the closest match in capacity. R417A is the simpler retrofit, because it usually keeps the existing oil. The best choice depends on the system and the job.

Is R407C a drop-in replacement for R22?
No. R407C needs POE oil, so you must change the oil. You also need to charge it as liquid and check the system settings.

Can I mix R417A with R22?
No. Never mix refrigerants. Recover all the R22 first, then charge the new gas.

Does R417A need an oil change?
Usually not. Its hydrocarbon component helps return mineral oil to the compressor. However, always check the gas and compressor manufacturers’ guidance.

Can I put R410A in an R22 system?
No. R410A runs at much higher pressures than R22 equipment can handle.

Is R22 banned in the UAE?
No. R22 is still legal to buy and use, but supply is shrinking under the Montreal Protocol phase-down.

Summary

  • R407C and R417A are the main R22 replacement gases in the UAE.
  • R407C offers capacity close to R22, but it needs POE oil.
  • R417A usually keeps the existing oil, but it gives slightly less capacity.
  • Both are blends, so always charge them as liquid.
  • Neither R410A nor R32 can go into an R22 system.
  • Replace the system instead if the compressor has failed or the unit is near the end of its life.

Haste Trading supplies R407C, R417A, oils and retrofit parts across Dubai, Sharjah, Abu Dhabi and the wider UAE. Browse our refrigerant range or contact our team for advice on your system.

This guide draws on refrigerant manufacturer data and retrofit guidance. Always follow the manufacturer’s instructions for your specific equipment.